Energy supply and dense energy storage

When is a linear optimal power flow safe to dispatch from, and which cheap AC repair makes it safe?

research/grid-linopf

Research programme on linear OPF dispatch feasibility on the PGLib-OPF benchmark: the DC dispatch overloads branches on all 11 congested cases; a trust-region successive linearisation of the AC power flow repairs 7 of 11 at the AC optimum's cost, and on 12 held-out angle-limited (SAD) cases the same rules with linearised angle rows repair 7 of 11 (angle-blind: 3); at the AC optimum's voltage schedule (an oracle)…

What it found

An open research programme (opened 2026-11-12, track 21) on whether the dispatch from a linear optimal power flow, the model markets clear energy with, is feasible once the AC physics is applied, and how many AC power flows a repair needs to make it so at the AC optimum's cost. Benchmark: PGLib-OPF v23.07 (typical, congested API and small-angle-difference SAD sets of 12 cases, 14 to 300 buses), solved with PYPOWER, whose AC optima match the library's published values within 0.005 %.

So far (experiments in infra-dcopf): the plain DC dispatch overloads branches on all 11 API cases with an AC optimum; a trust-region successive linearisation (finite-difference loss factors and flow sensitivities, a QP, an elastic l1 fallback) repairs 7 of 11 at the optimum's cost, with rules set on those cases; on the 12 SAD cases, held out, the same rules plus linearised angle-difference rows repair 7 of the 11 with an AC optimum, while the angle-blind version repairs 3 and lands 6.5–17.6 % below the optimum's cost by breaking up to 16 angle limits.

Milestone 3 (2026-11-12): without that oracle schedule, at PGLib's own 1.0 pu setpoints, the same repair clears thermal, slack and angle limits on 2 of 11 API and 2 of 11 SAD cases (6 and 7 with it), none of its dispatches meets voltage and Q limits, and an AC OPF over voltages only after it makes 16 of 34 cases fully feasible at a mean 0.8–4.3 % above the optimum's cost.

Milestone 3b (2026-11-12): a successive linearisation over P and the generator voltage setpoints, with voltage and Q limits as linear rows, is fully feasible on only 5 of 34 cases as pre-registered (it stops within 0.1 % of the limits on 19); with a small margin inside every limit (a variant chosen after that result) it is fully feasible on 18 of 34, and on 28 of 34 with the voltage-only stage after it, at a mean 0.17–0.34 % above the AC optimum's cost; not yet tested on held-out cases.

Show the rest of the summary (10 more paragraphs, 880 words)

Milestone 2 (2026-11-13): the same sensitivities from the power-flow Jacobian (one sparse solve per round, matching central differences to 1.3×10−5) give 19 and 29 of 34, so the counts do not hang on finite-difference noise; the run time falls only 1.1× because the QP takes 98–99 % of it, and a finished repair's cost moves by up to 3.1 points with the derivative source, since the method stops at its first feasible round.

Milestone 2b (2026-11-13): every QP the repair poses (347) re-solved by Clarabel as a referee: where PIPS reports a solution it is the right one (objectives agree within 10−6), but PIPS fails on 36 of 99 elastic QPs, 26 of them solvable; with Clarabel on every QP the repair is fully feasible on 21 of 34 (31 with the voltage-only stage), loses no case, and runs about 5× faster.

Milestone 4a (2026-11-13): LPAC-C (Coffrin and Van Hentenryck 2014, PowerModels' conic form), solved once and run through one AC power flow, is fully feasible on 0 of 34 cases; it has no solution on 9 (7 of the 11 SAD cases; a second solver agrees on 8), and where it solves the AC power flow breaks Q limits on 21 of 25, with 376 of 1,000 generator voltage setpoints exactly on a bound. As a starting point for the repair it is about as good as the DC dispatch (17 against 15 fully feasible on the 25 cases it solves).

On 244 load-perturbed copies (every bus’s load × 0.9 to 1.1, 10 seeds) the repair is fully feasible on 0.66 (95 % cluster bootstrap 0.52 to 0.79) and 0.91 with the voltage stage (0.83 to 0.97), its one-load-point verdict matches the copies’ majority on 30 of 34 cases, and it beats the voltage stage on the DC dispatch on 29 cases with no losses (P = 3.7e-9); 101 of 360 copies, 71 of 120 congested ones, have no AC optimum and are excluded.

Milestone 7, empirical half (2026-11-13): traced round by round with a 30-round budget instead of 10, the repair alone is fully feasible on 31 of 34 cases (by round 20; 21 at 10 rounds), the ten late finishers at a mean +0.41 % over the AC optimum; 168 of 224 misses in rounds 1–10 are curvature failures (the step’s second-order error exceeds the margin, on thermal and Q rows), the one-step finishing condition holds on all 190 hard misses, and the convergence bound H4 as written is refuted (10× or more off on 25 of 31 finishers; case73 API stalls with a well-conditioned Jacobian at a point of local infeasibility).

Limits: one AC solver, few congested copies with an AC optimum, no baseline yet from LPAC-W or optimised linearisations. Target: IEEE Transactions on Power Systems.

Milestone 6 (2026-11-13): on the 24 held-out PGLib cases of 500 to 2,000 buses (12 scorable; PIPS has no AC optimum on 11), the frozen repair is fully feasible within 10 rounds on 0 of 12, refuting H2 as written; within a 20-round budget fixed beforehand on 6 of 12, and 8 of 12 with the voltage stage (DC dispatch with the same stage: 0), at a mean +0.66 % over the AC optimum. Past the loading limit (2026-11-14): on the six cases whose DC dispatch has no AC power flow, the power-flow Jacobian’s smallest singular value falls to 5 to 9 % of its no-load value where load continuation stalls, a saddle-node fold; repair-and-continue reaches a feasible point on case300 TYP (+0.83 %) and none of the five RTE cases.

The slack, not the dispatch (2026-11-15): with the reference moved from PYPOWER’s choice (a 15 to 30 MW unit carrying 505 to 687 MW of losses) to the largest unit, the DC dispatch has an AC power flow on all five RTE networks and the frozen repair is fully feasible on 3 of 5 at +0.02 to +0.62 %; IPOPT swapped in under PYPOWER’s unchanged AC OPF solves all 12 large cases PIPS cannot, within 0.005 % of PGLib’s published objectives.

Milestone 6 under one protocol (2026-11-15): on all 24 held-out cases, with the slack at the largest unit, IPOPT for the reactive stage and PGLib’s objective as reference, the frozen repair is fully feasible on 10 of 24 within 20 rounds and 12 of 24 with the reactive stage, against 0 of 24 for the DC dispatch, with no case lost against the earlier protocol; clean points cost a mean +0.50 % (one above +1 %), and five cases have no DC OPF solution.

Convergence (milestone 7, theory half, 2026-11-17): if the power flow is smooth along each step and every hard QP is feasible, a step shorter than a curvature radius finishes the repair and the trust region is halved at most log2(box / radius) times (1 to 12 on the traces, 0 to 5 observed); most rounds (162 of 228 misses) are accepted cost-driven steps that no assumption bounds a priori, and logging the elastic QP's own penalty shows the case73 API stall is a local infeasibility of the repair's controls (voltage violation within 1.6 × 10−5 of stationary), while case118 API stalls on the acceptance test (worst versus summed overload); accepting on the penalty changes no verdict.

Research log

Ongoing: each run adds a batch and an entry, newest first. Source: LOG.md.

2026-11-19 · Rule E-once: outcome. 0 repeats and case73 API still clean (round 12, +3.26 %), but a two-round cycle (rejected widened step, tiny accepted elastic step that re-arms the rule) loses case30 API and held-out case793 API; development 31 of 34 (as frozen), held-out 9 of 19 (frozen 10). Not adopted

2026-11-19 · Rule E-once: enlarge the box at most once per base point (plan)

2026-11-19 · Box enlargement before the elastic fallback: outcome. case73 API clean at round 12 (+3.26 %) under the full margins, but 68 of 94 firings rebuild the QP just rejected; development 31 to 30 of 34, held-out 10 to 8 of 19. Not adopted

2026-11-19 · Box enlargement before the elastic fallback (plan)

2026-11-19 · Why is the hard QP infeasible on the development stalls? Outcome. The trust box, not the margins: the linearised set without the box is non-empty on all 58 failed rounds

2026-11-19 · Why is the hard QP infeasible on the development stalls? An IIS of every round (plan)

Show 25 earlier entries

2026-11-18 · A merit that matches the QP: outcome. Inert in development (31 of 34 either way; case118 API still stalls, every round from 3 an elastic QP); held-out finishers 10 to 8 of 19, cheaper by 0.13 points where both finish. Not adopted

  • Plan, outcome and Next: research/infra-dcopf/LOG.md (2026-11-18); numbers in research/infra-dcopf/experiments/results_summerit.txt. S2, S3, S4, S5 held; S1, S6 refuted.
  • The merits disagree on 5 trials in development. case118 API's stall is the hard QP's infeasibility, not the acceptance test, which withdraws the 2026-11-17 reading. Held-out S loses case793 API and case588 TYP and is slower on 3 of 8 common finishers, but lands cheaper clean points (mean −0.13 points, up to −0.56). The frozen worst-excess merit stands.

2026-11-18 · A merit that matches the QP: accept a step on the summed thermal excess (plan)

  • Plan, rule S (the merit's worst thermal excess replaced by the summed excess, every round) and predictions S1 to S6: research/infra-dcopf/LOG.md (2026-11-18); script research/infra-dcopf/experiments/run_summerit.py. Frozen on the 34 development cases, scored on the 19 held-out cases that reach the repair.

2026-11-17 · A margin-backoff rule for an empty margin-shifted set: outcome. Development 32 of 34 (case73 API clean at round 8, +0.96 %), none lost; held-out it fires on 1 of 19 and changes no verdict

  • Plan, outcome and Next: research/infra-dcopf/LOG.md (2026-11-17); numbers in research/infra-dcopf/experiments/results_backoff.txt. B1, B2, B4, B5, B6 held; B3, B7 refuted.
  • Rule B fires on case73 API and case24 API (margins halved once). case73 API finishes for the first time; case24 API finishes two rounds sooner at +0.17 % instead of +0.71 %. case240 TYP and SAD stay empty at an eighth of the margins, so the rule declines and their frozen finishes stand.
  • Held-out it fires only on case588 API: same round (19), cost +0.66 % instead of +0.87 %. The two-solver panel prevented PIPS-only firings on case179 SAD and case793 API. The check costs up to 57 minutes on a 1,354-bus case, so it is a stall diagnostic, not a per-case step.

2026-11-17 · A margin-backoff rule for an empty margin-shifted set (plan)

  • Plan, rule B (a two-solver check of the margin-shifted AC OPF before round 1; on an empty set, halve every margin up to three times) and predictions B1 to B7: research/infra-dcopf/LOG.md (2026-11-17); script research/infra-dcopf/experiments/run_backoff.py. Frozen on the 34 development cases, scored on the held-out 24.

2026-11-17 · Do the two development stalls come from the repair's own safety margins? Outcome. case73 API: its margin-shifted AC OPF has no solution on PIPS or IPOPT; case118 API: it solves; zero margins finish neither and lose 5 to 21 finishers

  • Plan, outcome and Next: research/infra-dcopf/LOG.md (2026-11-17); numbers in research/infra-dcopf/experiments/results_margin.txt. A1, M2, Z3 held; M1, M3, Z1, Z2, Z4 refuted. Reproduction gate passed on all 34 cases.
  • case73 API's AC optimum sits on its voltage bounds (all 14 generator buses at the ceiling, 7 PQ buses at the floor) and 10 branch ends at their rating; pulling in thermal and voltage bounds together leaves no AC point (each alone is solvable, +0.41 % and +1.99 %). The repair stalls because it aims at an empty set.
  • The shifted OPF is empty on 4 of 34 cases by both solvers, and the repair still finishes 3 of them; the 0.001 pu voltage margin costs up to +6.9 % (case57 API) at the shifted optimum.

2026-11-17 · Do the two development stalls come from the repair's own safety margins? (plan)

  • Plan and predictions A1, M1 to M3 (margin-shifted AC OPF) and Z1 to Z4 (the repair with margins removed): research/infra-dcopf/LOG.md (2026-11-17); script research/infra-dcopf/experiments/run_margin.py.

2026-11-17 · What stalls the repair on case73 and case118 API: outcome. case73 API is a local infeasibility of the repair's controls (the l1 voltage violation is within 1.6 × 10<sup>−5</sup> of stationary); case118 API is the acceptance test; acceptance on the penalty changes no verdict

  • Plan, outcome and Next: research/infra-dcopf/LOG.md (2026-11-17); numbers in research/infra-dcopf/experiments/results_elastic.txt. S1, S2, V1 refuted; S3, S4, V2 held.
  • On case73 API from round 22 the elastic QP can lower the margin-shifted voltage violation by at most 8.8 × 10<sup>−6</sup> at any box scale from 1 to 10<sup>−3</sup>: two PQ buses sit up to 0.002 pu below V<sub>min</sub>, 14 of 33 setpoints are on their upper bound and the lines on their margins. Proposition 2 applies; the earlier Q7 reading (not stationary, because the step scales with the box) is withdrawn: the step moves along directions that leave the violation flat.
  • On case118 API every late elastic step lowers the QP's penalty (sum of overloads) and is rejected by the merit (worst overload). Accepting elastic rounds on the penalty instead finishes neither case and loses none of the 31 development finishers (one finishes a round later, +0.68 % instead of +0.34 %).

2026-11-17 · Is case73 API's stall a stationary point of the elastic penalty? (plan)

  • Plan and predictions S1 to S4 (arm T, the elastic QP's own penalty logged per round with a box probe) and V1, V2 (arm P, acceptance on the penalty on elastic rounds): research/infra-dcopf/LOG.md (2026-11-17); script research/infra-dcopf/experiments/run_elastic.py.

2026-11-17 · Milestone 7, theory half: a step-based convergence statement replacing H4. Halvings bounded by a logarithm (H* ≤ 12); accepted rounds, 162 of 228 misses, have no a priori bound; case73 API's stall is not first-order stationarity

  • Statement and proofs: theory.md (Proposition 1, Theorems 1 to 3, Proposition 2; assumptions A1 smooth power flow along the steps, A2 hard-QP feasibility). Plan, predictions Q1 to Q7 and outcome: research/infra-dcopf/LOG.md (2026-11-17); numbers in research/infra-dcopf/experiments/results_theory.txt (from the 2026-11-13 traces, no new solves).
  • Q1 to Q4 held: halvings never exceed Ĥ* (range 1 to 12, observed 0 to 5); the finishing step is inside the worst-case radius on only 4 of 31 finishers; steps shrink before the finish on 28 of 28. Q5 to Q7 refuted: round 1's curvature does not predict the path (15 of 39); the path-length bound is 24x loose (median); case73 API's elastic step scales with its box over a 250-fold halving, so Proposition 2's d = 0 hypothesis is not met, which corrects the 2026-11-13 "stationary point" reading.
  • Next: log the elastic penalty decrease on case73 and case118 API; a box tied to the violation (makes the accepted-round count a priori), held-out; acceptance on the elastic QP's own penalty.

2026-11-16 · The five unscored cases with a second-solver start: outcome. 13 of 24 with the reactive stage (was 12); J alone stays at 10

  • Plan and outcome: research/infra-dcopf/LOG.md (2026-11-16); numbers in research/infra-dcopf/experiments/results_dc_rescue.txt.
  • E1 (full-load power flow on at least 3 of 5) and E2 (J clean on at least 1) refuted: 2 of 5 and 0 of 5. case2000 API ends J one Q limit short and the IPOPT reactive stage makes it fully feasible at +0.193 %; case1951 API ends at one 104.5 % overload and its reactive stage hit the 45-minute limit. SNEM's warm-start angles were NaN (the x = 0 ties); with them fixed (declared variant) the continuation stalls at 75 to 84 % of load.
  • Next: a certifying DC solver for every case's start, the SNEM stall, the near misses, the post-feasibility cost phase.

2026-11-16 · Why the DC OPF has no solution on five held-out cases: outcome. On 4 of 5 the reference DC solver fails, not the network

  • Plan, outcome and the follow-up plan: research/infra-dcopf/LOG.md (2026-11-16); numbers in research/infra-dcopf/experiments/results_dc_infeasible.txt.
  • A second solver (the same B-theta DC OPF on Clarabel) agrees with PYPOWER's PIPS on all 89 problems both solve (within 1e-5) and solves 26 that PIPS reports as having no solution. case2000_goc API is feasible under MATPOWER's own convention; the SNEM network has two x = 0 bus ties that make MATPOWER's B infinite, and with them at 1e-4 pu its DC OPF solves; case1951_rte API is the one genuine case, infeasible by 1.61 MW on one rating row under b = 1/(x tap) and feasible under PowerModels' convention.
  • D1 (PM on PIPS matches PGLib) and D2 (ratings cause it) refuted as written; D4 held on Clarabel. Next: the five cases through the unchanged repair from a second-solver start (E1 to E3).

2026-11-16 · Why the DC OPF has no solution on five held-out cases (plan)

  • Plan and predictions D1 to D4 with control C0: research/infra-dcopf/LOG.md (2026-11-16); script research/infra-dcopf/experiments/diag_dc_infeasible.py. The five unscored cases (case1803_snem x3, case1951_rte API, case2000_goc API): data, ratings, angle limits or the DC convention?

2026-11-15 · Milestone 6 under one protocol: outcome. 10 of 24 fully feasible within 20 rounds, 12 of 24 with the IPOPT reactive stage, none lost against the earlier protocol

  • Plan, predictions and outcome: research/infra-dcopf/LOG.md (2026-11-15); numbers in research/infra-dcopf/experiments/results_heldout_slack.txt.
  • One protocol on all 24 held-out cases: reference at the largest live unit, DC start, continuation to the full-load power flow, frozen 20-round J-m-a, IPOPT reactive stage, cost against PGLib's published objective. Controls: identical statuses on the 6 cases whose reference does not move, and on the 5 RTE cases of the previous step.
  • R1 to R4 and R6 held, R5 refuted. Scored 19 of 24 (5 have no DC OPF solution: SNEM x3, case1951 API, case2000 API). J fully feasible on 10 of 24, J or J+R on 12 of 24 (DC dispatch: 0); paired on the 19 the earlier protocol scored, 3 gained and 0 lost. Clean points +0.01 to +2.12 %, mean +0.50 %; only case588 TYP above +1 %. H2 as written stays refuted (1 of 24 within 10 rounds).
  • Next: why the DC OPF has no solution on five cases; the post-feasibility cost phase; the restated convergence theorem.

2026-11-15 · Milestone 6 under one protocol (plan): all 24 held-out cases with the slack at the largest unit and the PGLib/IPOPT reference

  • Plan and predictions R1 to R6 with controls C0, C1: research/infra-dcopf/LOG.md (2026-11-15, "Held-out cases under one protocol"); script research/infra-dcopf/experiments/run_heldout_slack.py.

2026-11-14 · Milestone 6 Next (1) and (2): the stall is a fold on all six; repair-and-continue clears case300 TYP only

  • Plan, predictions and outcome: research/infra-dcopf/LOG.md (2026-11-14, "Past the loading limit"); numbers in research/infra-dcopf/experiments/results_fold.txt and results_fold_fallback.txt; figure fold_sigma.svg.
  • Fold test, F1 to F3 held: the Newton Jacobian's smallest singular value falls to 5 to 9 % of its no-load value at every stall, σ<sub>min</sub><sup>2</sup> is linear in load near it (R<sup>2</sup> ≥ 0.996) with the fitted fold 0.001 to 0.004 past the stall, and the AC-optimum control keeps 84 % at full load. The DC dispatch at the file's voltage setpoints is past the loading limit on all six.
  • Repair-and-continue, M1 to M3 and M5 refuted: repaired at the fold, round 1's linearisation has no power flow on any case, and the RTE stages end at points breaking hundreds of voltage limits. With a fallback declared after the run (re-solve the repaired point cold), case300 TYP walks up in four stages and is fully clean at full load at +0.83 % (M4 held), the first feasible point from the DC start on a no-power-flow case. The five RTE cases stay unsolved.
  • Next: a reactive (V, Q) pre-stage at the fold point before the P repair, or the reduced-load AC OPF's voltage schedule as the start, on the same six; then the second reference AC solver.

2026-11-14 · Milestone 6 Next (1): a start with an AC power flow. The planned dispatch homotopy fails at its first point; the DC dispatch looks past the loading limit on all six no-power-flow cases

  • Plan, predictions and outcome: research/infra-dcopf/LOG.md (2026-11-14); numbers in research/infra-dcopf/experiments/results_homotopy.txt, results_homotopy_load.txt, results_homotopy_dcangle.txt.
  • Planned run: dispatch homotopy from the case file's dispatch to the DC point. Q1 to Q4 refuted (0 of 6), Q5 untestable. PGLib's file dispatch is not an operating point (generation 2.0 to 18.3 GW, 3 to 23 %, short of load), and it has no power flow on any of the six cases.
  • Declared diagnostics: Newton from DC power-flow angles solves all six at no load (PYPOWER and pandapower fail from flat starts on the RTE networks). Scaling load and the DC dispatch up together then stalls at 48 to 85 % of load on every case, with the lowest voltage falling to 0.72 to 0.79 pu, which looks like the nose of a loadability curve. On case300 TYP the AC optimum's dispatch at the same voltage setpoints reaches full load, so the DC dispatch is the obstacle.
  • Reading: the RTE failures are decided before the first QP, as milestone 6 said, and no power-flow start fixes them. The start must move the dispatch or the voltages. Next: a load-continuation repair (J at μ*, then step μ up), and a Jacobian fold test.

2026-11-13 · Milestone 6: held-out 500 to 2,000-bus cases. H2 as written refuted (0 of 12 within 10 rounds); 6 of 12 within 20, 8 of 12 with the voltage stage

  • The eight PGLib-OPF v23.07 networks of 500 to 2,000 buses, TYP, API and SAD (24 cases no rule was set on), with J-m-a frozen and the 20-round budget fixed by milestone 7. Pre-registered (plan, two amendments made before any repair outcome was read, and the outcome are in research/infra-dcopf/LOG.md; numbers in research/infra-dcopf/experiments/results_heldout.txt).
  • Scaling fix first: the full QP did not finish one case in 25 minutes at 2,000 buses. Constraint generation on Clarabel reproduces the full-QP repair exactly on all 34 development cases (same statuses round by round, 0.0000 pp cost difference) at 11x the speed, and is what ran.
  • Scored 12 of 24. PIPS's optima match PGLib's within 0.004 % where it solves (13 cases); none on the SNEM and RTE networks or on case588 and case1354 API; case2000 API has no DC start.
  • H1 held (DC breaks a thermal, slack or angle limit on 7 of 7 scored API and SAD cases). H2 as written refuted: fully clean within 10 rounds on 0 of 12 (development 21 of 34). Within 20: 6 of 12 (all at round 14 to 20). With the voltage stage: 8 of 12. J+R beats S+R 8 to 0 (P = 0.0078). Mean cost of clean points +0.66 % (bar +0.5 %, refuted).
  • Elastic QPs rise to 44 % of rounds from 29 %; the DC starts break Q limits on 14 to 118 units (development 0 to 26), and the SAD starts need the DC OPF without angle limits.
  • After-the-run diagnostic on the 11 unsolved cases, against PGLib's published objective: case588 API clean at round 15 (+0.95 %); on five RTE cases the AC power flow at the DC start does not converge, so the repair never starts.
  • Next: a start with an AC power flow (damped or homotopy Newton from the DC point); a round budget or stopping rule scaled to the start's violation, set on development cases only; a second reference AC solver for the 11 unsolved cases.

2026-11-13 · Milestone 7 (empirical half): a 30-round budget clears 31 of 34; misses are curvature, one stall is local infeasibility; H4 as written refuted

  • Frozen J-m-a traced round by round with a 30-round budget on the 36 PGLib cases (pre-registered; plan and outcome in research/infra-dcopf/LOG.md, numbers in research/infra-dcopf/experiments/results_converge.txt). First 10 rounds reproduce the nominal run exactly.
  • Budget: fully clean on 31 of 34 within 20 rounds (10 rounds: 21), the ten late finishers at +0.41 % mean cost over the AC optimum. The repair alone matches what repair-then-voltage-stage got at 10 rounds.
  • Mechanism: 168 of 224 misses in rounds 1 to 10 are curvature failures (hard QP, remainder above the margin), on thermal and Q rows; the one-step finishing condition (Proposition 1: a row breaks only if its second-order remainder exceeds its margin) holds on all 190 hard misses.
  • H4 as written refuted: its bound 1 + k* + φ<sub>0</sub>/δ<sub>min</sub> is within 10x of the observed rounds on 6 of 31 finishers (up to 55,000x off), the curvature estimate varies by more than 10x along the path on half the cases, and case73 API stalls with a nonsingular Jacobian at a point of local infeasibility (all 30 QPs elastic, merit flat from round 14). The theory needs a hard-QP-feasibility assumption and a step-based, not decrease-based, statement.
  • Next: milestone 6 with the budget frozen at 20 rounds; the convergence statement rewritten (theory half of milestone 7); per-row curvature-scaled margins, held-out only.

2026-11-13 · Milestone 5: load-perturbed copies. The counts hold on feasible copies; 101 of 360 copies have no AC optimum

  • 360 copies of the 36 PGLib cases (seeds 0 to 9, every bus's load x U[0.9, 1.1], constant power factor), frozen arms, pre-registered (plan and outcome in research/infra-dcopf/LOG.md; numbers in research/infra-dcopf/experiments/results_perturb.txt).
  • On the 244 scored copies of the 34 base cases: J-m-a fully clean 0.660 (cluster bootstrap over base cases 0.52 to 0.79; nominal 0.62), with the reactive stage 0.906 (0.83 to 0.97; nominal 0.91). Nominal verdict = majority verdict on 30 of 34 cases. J+R beats the reactive stage on the plain DC dispatch on 29 cases and loses none (sign test P = 3.7e-9). Mean cost of clean points +0.08 / +0.23 / +0.69 % (TYP / API / SAD). All five predictions held.
  • Caveat: PIPS finds no AC optimum on 101 copies, 71 of the 120 API ones (31 of those with less total load than nominal). Running the arms on them anyway (a declared after-the-run diagnostic) finds a feasible point on only 4, so most are probably infeasible, but the API intervals rest on 42 copies.
  • Fragility sits in the round budget: nominal finishers at round 8 or later stay clean on 0.68 of copies, earlier finishers on 0.97.
  • Next: milestone 6 (held-out 500 to 2,000-bus cases), the post-feasibility cost phase, a round-budget sweep, the rest of milestone 4.

2026-11-13 · Milestone 4a: LPAC as a one-shot baseline. Fully feasible on 0 of 34; no solution on 9

  • LPAC-C (Coffrin and Van Hentenryck 2014, the conic form of PowerModels' LPACCPowerModel), built in infra-dcopf/src/infra_dcopf/lpac.py and solved by Clarabel with SCS as a second opinion, then its P and voltages run through one AC power flow. Pre-registered (plan in research/infra-dcopf/LOG.md).
  • H3 held, strongly: the one-shot LPAC dispatch is fully feasible on 0 of 34 PGLib cases (bar: at most 10; J-m-a: 21). On the 25 cases it solves, the AC power flow breaks Q limits on 21 and voltage limits on 20, and 376 of 1,000 units get a setpoint exactly on a voltage bound; P-clean on 4 (DC: 3). With the reactive stage after it, 8 of 34 (J-m-a+R: 31).
  • LPAC-C has no solution on 9 of 34, 7 of the 11 SAD cases among them (SCS agrees on 8, inconclusive on 1). After-the-run diagnostic: removing the angle limits makes 8 of the 9 solvable.
  • As a warm start for the frozen repair: 17 of the 25 LPAC-solvable cases fully clean against 15 from the DC start (5 gained, 3 lost, sign test P = 0.73); 24 against 23 with the reactive stage; finishes earlier on 7 of the 12 both finish.
  • P1, P2, P3 refuted (P-clean 4 against a bar of 10; objective within 1 % on 16 against 27; with the reactive stage 8 against 15); P4 refuted as written (17 of 34, since 9 cases have no start). Numbers: research/infra-dcopf/experiments/results_lpac.txt, results_lpac_infeasible.txt.
  • Next in milestone 4: LPAC-W (warm start, needs an AC base point) and the polyhedral LP form, then the one-shot optimised linearisation (Misra et al. 2018 or Chen and Singh 2025).

2026-11-13 · Milestone 2b: is the repair's QP solved correctly? PIPS fails on solvable elastic QPs; Clarabel adopted

  • Every QP J-m-a poses on the 34 PGLib cases (347: 248 hard, 99 elastic) re-solved by Clarabel 0.11 as a referee and by a screened (constraint-generation) PIPS solve. Wherever PIPS reports success, its objective matches Clarabel's within 1e-6 (236 of 236), so finished repairs and their costs stand; screening is exact (228 of 228) on 7.8 % of the rows.
  • PIPS's hard-QP failures are mostly real (Clarabel solves 5 of 75). Its elastic failures are not: 36 of 99, of which Clarabel solves 26. The repair had treated them as rejected steps.
  • With Clarabel on every QP, J-m-a is fully clean on 21 of 34 (PIPS: 19) and 31 of 34 with the reactive stage (29); the two gains are case24 API and case73 SAD, no case is lost, and costs where both finish are unchanged. Repair time 1,353 s to 260 to 277 s (4.9 to 5.2x; the 5x prediction sits within timing noise). Screened PIPS: 21 and 29, 2.99x.
  • For the programme: later milestones (4's baselines, 6's 500 to 2,000-bus held-out cases) run on Clarabel. Still open in 2b: a post-feasibility phase for the path-dependent cost (milestone 2's H3).
  • Plan, predictions and outcome: research/infra-dcopf/LOG.md.

2026-11-13 · Milestone 2: analytic sensitivities from the power-flow Jacobian

  • vlin.jacobian_sens gives the repair's sensitivities (slack P, branch |S| at both ends, angle differences, PQ-bus voltages, unit Q, with respect to unit P and generator voltage setpoints) from the Newton Jacobian at the base point: one sparse LU per round instead of n_gen + n_vbus power flows. It matches central differences to 2.3e-6 (scaled) on 32 of 34 cases and to 1.3e-5 on the other two once the difference step is refined (results_sens.txt).
  • Re-running J-m with it on all 36 PGLib cases: fully clean 19 of 34 (finite differences: 18), 29 of 34 with the reactive stage (28); same verdict on 31. The counts are robust to the derivative source.
  • Two assumptions refuted: (1) run time fell only 1.1x, because PIPS's QP over 758 to 2,452 rows takes 98 to 99 % of each repair; the power flows were never the bottleneck. (2) The cost of a finished repair moved by over 0.05 pp on 6 of 17 cases, worst 3.08 pp: the method stops at the first clean round, so its cost depends on the path. For the paper, H2's "at the AC optimum's cost" needs a post-feasibility phase; milestone 6 (larger cases) needs a sparse or screened QP first.
  • Plan, predictions and outcome: research/infra-dcopf/LOG.md; numbers: results_vlin_margin_analytic.txt.

2026-11-12 · Milestone 3b: voltage setpoints as decision variables

  • A successive linearisation over P and the generator voltage setpoints, with thermal, slack, angle, bus-voltage and Q rows (infra-dcopf/src/infra_dcopf/vlin.py), run from the plain DC dispatch at 1.0 pu on all 36 PGLib TYP, API and SAD cases. Pre-registered as planned (J), it is fully clean on only 5 of 34: it ends within 0.1 % / 0.1 MVAr of every limit on 19 but rarely strictly inside (H1 and H2 refuted; plan and outcome in research/infra-dcopf/LOG.md). The 5 it finishes cost +0.0 to +0.13 % on average against the AC optimum.
  • A declared, post-hoc variant (J-m) pulls every QP bound slightly inside its limit (0.1 % of rating, 0.1 MW, 0.01 deg, 0.001 pu, 0.1 MVAr): 18 of 34 fully clean on its own, and 28 of 34 with milestone 3's reactive stage on its misses, at mean +0.17 to +0.34 % against the AC optimum. Milestone 3's best non-oracle pipeline (F+R) got 16 at +0.8 to +4.3 %. On SAD, J-m alone (8 of 11) beats the P-only repair run at the oracle schedule (6).
  • For the programme: H2 (a few relinearisations repair the dispatch) now has a non-oracle form that works on most cases, but it was tuned on these cases. Before the paper relies on J-m, it needs the held-out run (milestone 6, the larger PGLib cases, rules frozen as committed here) and the LPAC and optimised-linearisation baselines (milestone 4). Cost per round is n_gen + n_vbus power flows. Analytic sensitivities (milestone 2) matter more now: case300 API takes 10 minutes.

2026-11-12 · Milestone 3: a voltage schedule not from the AC optimum

  • At PGLib's own 1.0 pu setpoints instead of the AC optimum's, the frozen angle-aware repair (C-ang) is clean on thermal, slack and angle limits on 8 of 12 TYP, 2 of 11 API and 2 of 11 SAD cases (oracle schedule: 7, 6, 7), and none of those dispatches meets V and Q limits. A reactive stage (AC OPF over V and Q, non-slack P pinned) makes 16 of 34 fully feasible (oracle run: 17 fully clean) at a mean 0.8 to 4.3 % above the AC optimum's cost; on the plain DC dispatch it makes 4. Predictions H2 and H4 held, H1, H3 and H5 refuted (details and plan in research/infra-dcopf/LOG.md; numbers in results_vsched.txt).
  • For the programme: H2 (a few relinearisations repair the dispatch) has so far been tested only with the oracle voltages, and without them it fails on the binding sets. The repair has to move voltage setpoints with P. Proposed new milestone 3b, before LPAC baselines: VG as decision variables in the linearisation (sensitivities of flows, angles, slack, V and Q to VG), scored at the case-file start on all three sets.

2026-11-12 · Programme opened; milestone 1 (held-out SAD test) landed

  • Opened from track 21's draw: no open programme covered the grid, and infra-dcopf had grown into a programme's worth of steps (DC error, loss factors, PGLib validation, successive linearisation). The question is narrowed to dispatch feasibility and repair budget on held-out benchmark sets, which the accuracy and optimised-linearisation literature (Stott et al. 2009; Dvijotham and Molzahn 2016; Misra et al. 2018; Chen and Singh 2025) does not report.
  • Milestone 1: the API-tuned successive linearisation, run unchanged with linearised angle rows, is clean on 7 of 11 held-out SAD cases (prediction at least 8: refuted narrowly); angle-blind, 3. Plan, predictions and outcome in research/infra-dcopf/LOG.md, numbers in research/infra-dcopf/experiments/results_sad.txt.
  • Next: milestone 2 (analytic sensitivities) or 3 (a non-oracle voltage schedule); 3 matters more for the claim, since every result so far holds voltages at the AC optimum's schedule.

Paper, code and results

More in Energy supply and dense energy storage

All 41 Energy supply and dense energy storage projects →

Other research topics

Proper scoring & elicitation28Effort & peer prediction9Verification games & slashing19Detection & tolerances15Markets as routers13Prediction-market design9Paying contributors8Decentralised training systems23Digital twins & sim-to-real164LLM chip design loops40Robot manufacturing loops53Ambient AI assistant46Self-replicating manufacturing34Simulation-first design64Engineered clothing45Task-specific AI accelerators40Algorithmic chip-design loops42Open-source purpose-built robots50The software-engineering loop43Adversarial human imitation41Open-source residential construction41Autonomous multi-angle capture35Sensing, imaging and 3D33Energy supply and dense energy storage41Robot societies among people32Agentic co-design of low-cost robots28Laundry-hanging robots26Machine learning on qualitative data23Robots on the building site28Civilizations & group psychology3History & human sciences4