Energy supply and dense energy storage

How wrong is the DC approximation of optimal power flow on the IEEE 30-, 39- and 118-bus cases?

research/infra-dcopf

DC against AC optimal power flow in pandapower on the IEEE 30-, 39- and 118-bus cases: the DC model's cost is 1 to 3 % below the AC optimum (it ignores losses); on the 118-bus case its dispatch is feasible but costs 0.7 to 1.7 % more than the AC optimum once losses are paid, and on the 39-bus case it breaks voltage limits (15 buses at 0.6 of load) at almost no cost difference (modelled benchmark, not a measured system; tightened-limit runs often had no solution). Feeding the AC losses back into the DC model (a loss-adjusted DC) brings the 118-bus cost estimate to within 0.6 to 1.2 % of the AC optimum, but repairs only 13 to 32 % of the dispatch's excess cost and none of case39's voltage violations.

8 tests

What it found

The DC optimal power flow is the workhorse of dispatch and price studies; how much does it lose against the AC OPF? On pandapower's MATPOWER cases with their own quadratic costs, load scaled 0.6 to 1.1, both OPFs are solved and the DC set-points are run through an AC power flow (slack pays the losses). IEEE 118-bus (no branch limit binds): DC cost is 1.9–2.9 % below the AC optimum and its dispatch costs 0.7–1.7 % above it, with no violations. IEEE 39-bus: DC cost 1.0–1.5 % below, dispatch within 0.06 % of the optimum but 15, 5 and 1 buses out of voltage limits at 0.6, 0.8 and 1.0 of load. IEEE 30-bus: DC 1.3–2.3 % below; at full load the DC dispatch overloads a branch to 111 % and is 0.31 % cheaper than the AC optimum, i.e. a violated constraint. Checks: a two-bus closed form and agreement of the cost function with pandapower. Limits: tightened-limit sweeps frequently returned no solution from the solver and non-convergence is not separated from infeasibility; 118-bus branch limits never bind so it is a losses-only comparison; no prices (LMPs), unit commitment or N-1; costs are the cases' own, not market prices. Modelled benchmark cases, not measured systems. Loss-adjusted DC (AC losses spread uniformly over loads, iterated 2–4 passes): the 118-bus cost estimate falls within 0.6–1.2 % of the AC optimum, but the AC cost of its dispatch is still 0.58–1.18 % above it (13–32 % of plain DC's excess recovered) and case39's voltage violations are unchanged; a uniform loss share fixes the price level, not the merit order.

A figure from its own output

Figure produced by research/infra-dcopf: gap_vs_load
infra-dcopf/experiments/gap_vs_load.svg, written by the project's own experiment code.

Paper, code and results

More in Energy supply and dense energy storage

All 39 Energy supply and dense energy storage projects →

Other research topics

Proper scoring & elicitation28Effort & peer prediction9Verification games & slashing19Detection & tolerances14Markets as routers13Prediction-market design9Paying contributors8Decentralised training systems23Digital twins & sim-to-real164LLM chip design loops40Robot manufacturing loops53Ambient AI assistant46Self-replicating manufacturing34Simulation-first design64Engineered clothing45Task-specific AI accelerators40Algorithmic chip-design loops42Open-source purpose-built robots44The software-engineering loop43Adversarial human imitation41Open-source residential construction41Autonomous multi-angle capture34Sensing, imaging and 3D31Energy supply and dense energy storage39Robot societies among people31Agentic co-design of low-cost robots27Laundry-hanging robots25Machine learning on qualitative data23Robots on the building site27Civilizations & group psychology1History & human sciences1

Produced with AI assistance (Claude). Results are from the code in this repository and are simulated or stylised unless the abstract says otherwise; nothing here implies affiliation with or endorsement by any lab, researcher or company cited. MIT licensed.