Keep this bid so it is still here when the customer calls back. Every number on this form is saved together, under a name you choose, along with the figure it gave you, and restoring one puts the whole job back exactly as you priced it. Mark each one won or lost when you hear — the ones you have not heard back on stay listed as waiting, with how long they have been out. Once a few have come back, this panel says how long yours actually take, and how many are still out past that. Once enough of them have been decided, it also says whether the bids you save here have been landing differently lately than they used to.
Kept in this browser only, on this site’s own storage. Nothing is uploaded, and clearing your browser data clears it — download a backup to keep a copy or open your bids on another device. Bids are kept per tool, so these are the ones you saved here.
Pick the stud and the wall, then type the hole, notch or drain pipe. You get the share of the stud it uses, the limit, and the smallest stud that takes it, from the same engine as the whole-house takeoff. Nothing leaves your browser.
Check every run in a whole house: framing, plumbing holes and the order in one takeoff
In a load-bearing 2x4 wall the commonly stated residential limit is 40% of the stud width: 1.4 in on a 3.5 in stud, with the edge of the hole at least 5/8 in from each face. In a non-bearing wall, or where the bored studs are doubled, the limit is 60%: 2.1 in. A 1.5 in hole in a bearing 2x4 is over the limit by 0.1 in; the same hole in a non-bearing 2x4 passes with 1 in left on each side.
A notch is limited to 25% of the stud width in a bearing or exterior wall (7/8 in on a 2x4, 1.375 in on a 2x6) and 40% in a non-bearing wall (1.4 in on a 2x4). A hole and a notch are never allowed at the same section of a stud. A 1 in notch in a bearing 2x4 is 28.6% and fails; the checker says it needs a 2x6.
Not through a single bearing 2x6. A 3 in DWV drain is 3.5 in outside; with the 1/8 in clearance the checker adds, the hole is 3-5/8 in, 65.9% of a 5.5 in stud. Even doubled (60%, 3.3 in) it fails, so the options are a 2x8 wall, a chase or furred-out wall, or running the drain where it crosses plates and joists instead of studs. Your plumber and inspector decide which.
They are the limits commonly stated for solid-sawn studs in IRC R602.6: bored holes 40% of the width in a bearing wall (60% in a non-bearing wall or in doubled studs, no more than two doubled studs bored in a row), at least 5/8 in of wood left at each edge, notches 25% bearing and 40% non-bearing. The edition your jurisdiction adopted, local amendments and engineered studs (LVL, I-studs, steel) can differ; the percentages are inputs in the whole-house tool, not hard-wired claims.