Keep this bid so it is still here when the customer calls back. Every number on this form is saved together, under a name you choose, along with the figure it gave you, and restoring one puts the whole job back exactly as you priced it. Mark each one won or lost when you hear — the ones you have not heard back on stay listed as waiting, with how long they have been out. Once a few have come back, this panel says how long yours actually take, and how many are still out past that. Once enough of them have been decided, it also says whether the bids you save here have been landing differently lately than they used to.
Kept in this browser only, on this site’s own storage. Nothing is uploaded, and clearing your browser data clears it — download a backup to keep a copy or open your bids on another device. Bids are kept per tool, so these are the ones you saved here.
Type the attic and the ratings printed on the vents you will buy. You get the net free area the 1/150 rule asks for and how much of it goes in a ridge vent and in soffit vents, from the same engine as the whole-house takeoff. Nothing leaves your browser.
Do the whole house: framing, roof and ventilation in one takeoff
A 24 x 40 ft attic is 960 sq ft. At the code's 1 sq ft of net free area per 150 sq ft of attic that is 922 sq in (6.4 sq ft). With a ridge vent taking half, the calculator gives 25.6 ft of ridge vent (7 four-foot pieces at 18 sq in per foot) and 9 soffit vents of 56 sq in each. At 1/300, where the code allows it, the need halves to 461 sq in.
IRC R806.2 asks for net free ventilating area of at least 1/150 of the attic floor area. It allows 1/300 where a Class I or II vapor retarder is on the warm side of the ceiling, or where 40% to 50% of the vent area is high (a ridge vent) and the rest low in the eaves. Which one applies to your house is for you and your building inspector; the calculator takes the ratio as your input.
Net free area (NFA) is the open airflow area after the louver, screen or baffle takes its share. Ridge vents are labelled in square inches per foot and soffit vents in square inches per unit. Type the figures from the product you will buy: the defaults here (18 sq in per foot, 56 sq in per 16 in unit) are placeholders, not any maker's numbers.
Air enters low and leaves high, so the roof moves air by temperature even with no wind. The calculator puts half the area at the ridge by default, and if the ridge is too short to supply that share it takes what fits and moves the rest to the eaves. With no ridge vent, all the area is low, which moves air only when wind pushes it.