Insulation calculator

Type the house and its openings. The framing engine places every stud, king, jack, header, cripple and plate, measures the open cavity between them, and counts batt bags and the whole-wall R-value. Nothing leaves your browser.


  

Add insulation to a whole-house framing takeoff

The method

  1. Place the framing. The same engine as the whole-house takeoff lays out studs, corner and tee backing, kings, jacks, headers, sills, cripples and plates.
  2. Subtract. Per wall, panel area less the area of every framed member and each opening's rough area is open cavity.
  3. Bags. Cavity plus waste, divided by the bag coverage you type, rounded up.
  4. Effective R. A parallel-path calculation: the cavity path and the framing path (wood at R-1.25 per inch) each add the same sheathing, drywall and air-film layers, then combine by area using the framing share measured from the placed members.

Questions

How many bags of insulation do I need for a 40 x 30 ft house?

For a 40 x 30 ft rectangle with 8 ft walls, one 3 ft door and two 3 x 4 ft windows framed in 2x4 at 16 in on center, the calculator finds 890 sq ft of open cavity. With 5% waste and bags that cover 88 sq ft, that is 11 bags. Change any figure to match your plan.

Is a 2x4 wall with R-15 batts really R-15?

No. Framing conducts heat around the batt, so the whole wall is lower than the label. With the studs, plates, headers and cripples this calculator places, framing is 17.3% of the opaque wall, and the R-15 cavity gives about R-13.1 (R-16.9 through the cavity alone). A 2x6 wall with R-21 batts comes to about R-17.8 by the same method.

How much insulation does framing take out of a wall?

Counted from the members placed rather than guessed: in the 40 x 30 ft example, framing takes 16.6% of the wall panel area in 2x4 walls and 17.3% in 2x6 walls, so the open cavity is a little over 80% of the panel. The common 25% framing-factor guess is more pessimistic than a layout with 16 in spacing and one door and two windows needs.

What is not counted?

Attic and ceiling insulation, rim joists, air sealing, windows and doors (their U-factors are yours to type), and compressed batts. Bag coverage and R-values come from your product's label, and the effective R uses typical handbook layer values you can replace. It is an estimate to check against your supplier, not an energy-code compliance check.