IDS Model Check writes a COBie handover workbook from an IFC model, and its sister tool IFC Quantity Takeoff takes each room's doors and windows off its wall area. Both use two sources to say which rooms an opening faces. One is the file's own space boundaries (IfcRelSpaceBoundary). The other is geometry: a point 20 cm either side of the opening, through its wall, tested against each room's solid.
On 25 public models the two agreed for 821 of 869 openings. In 20 cases geometry found a room the file did not name. The earlier run left those 20 open. This run looked at each one.
18 windows in a dental clinic. Every window in dental_clinic.ifc that has a space boundary names one space only: 2R01 ROOF or 2R02 ROOF. Those are spaces Revit modelled over the lower roofs, outside the second floor. None of the 18 names the office it is in. Geometry finds the office on one side at 20, 60 and 100 cm, and the roof space on the other side. The window sits inside the office's height band, and the file bounds the host exterior wall to both spaces. So the office had lost its window. Its net wall area was too high by the window's 1.7 m², and in the COBie sheet the window's room was the roof.
2 doors in a Dutch house. In schependomlaan.ifc one bedroom door is bounded to the hallway only, and that bedroom has no door in the file at all. The same door type one floor down is bounded to both the hallway and its bedroom. The other door, between a store and the entrance hall, names only the store. Every probe on the far side lands in the hall.
The change. When the file names an opening on one side only, the takeoff now runs the geometry test too. If geometry finds two rooms, and one of them is the room the file names, it takes the other as well. If geometry doesn't find the file's room, nothing is added. Before and after, on every row and room in the 25 files, exactly those 20 openings changed. So did 17 rooms, each losing a window's or a door's area from its net wall figure. Nothing else moved. The window's COBie Space cell now reads 2R02,2D20: the roof space and the conference room.
What is still open: whether a handover should list an outside space such as 2R02 ROOF in a component's Space cell at all. That depends on the client's COBie requirements, and a BIM manager would know. The method and every number are in eval/door-extra-room-2026-11-23.md.