IFC to COBie, and a COBie check before you hand over

The owner wants a COBie 2.4 workbook at handover, and their FM team rejects one with blank required cells, SerialNumber typed into the serial number column, or a component in a room that does not exist. Drop your IFC model to get the workbook and the list of what to fix; or drop a COBie workbook from any tool to check it. Nothing is uploaded.

Make or check a workbook

to write a COBie workbook from it
to check one another tool made
Options

What goes in each sheet

A value the model does not hold is left blank, never made up, and the QC lists it. Numbers stay in the model's units, which the Facility row names.

How it was checked

On 25 public IFC exports (Revit, ARCHICAD, Tekla and others), every file wrote a workbook. Rooms from geometry were checked against what the files say themselves: of 869 doors and windows that the file's own space boundaries pair with rooms, 791 got exactly those rooms from geometry alone, 37 one of their two, and 19 a room the file does not name. Of 1,227 components a file puts in a room, with that hidden, 935 were placed in the same room, 89 in another and 203 in none (left blank). On the Duplex model, IfcOpenShell's COBie exporter (ifcfm 0.9.0, its legacy preset; its current preset stops with an error on both files tried) writes the same number of floors, rooms, zones, types and components, and leaves the room of 38 components as n/a; here they are placed in rooms (method and numbers).