IFC to COBie in a browser tab, and the 38 doors nobody put in a room

IDS Model Check now writes a COBie 2.4 handover workbook from any IFC model, places components in rooms from geometry, and checks any COBie workbook.

At handover, an owner asks for COBie: one spreadsheet listing the building's floors, rooms, the kinds of product installed, each installed unit, and who wrote all of it. US federal owners and UK public projects require it. The FM team that receives it checks it, and sends it back when required cells are blank or a component sits in a room that does not exist.

IDS Model Check now writes that workbook from an IFC model in the browser tab, and checks any COBie workbook, whichever tool wrote it. Nothing is uploaded.

The room nobody filled in

COBie wants every component in a space. Revit puts doors, windows and most equipment on a level instead. In the Duplex model, one of the NBIMS common BIM files and set up for COBie, 38 of the 99 components sit on a storey and in no room.

IfcOpenShell's ifcfm, the open-source COBie exporter on PyPI, writes n/a in those 38 cells. (Its current cobie24 preset stops with a TypeError on both public models we tried in version 0.9.0. Its legacy preset works.)

The new export has a "from the geometry" option. It uses IFC Quantity Takeoff's room reader to put each component in the room its body stands in. A door or window gets the rooms on both sides, written 101,102 as COBie allows. All 38 Duplex components get a room.

Is the room right? The files can answer that. Many exports also write space boundaries: the authoring tool's own record of which rooms a door connects. We ran the geometry alone on 869 doors and windows that have them, across 25 public models:

  • 791 got exactly the rooms the file names;
  • 37 got one of their two rooms;
  • 19 got a room the file does not name;
  • 22 got none and stayed blank.

For other components we hid the room the file gives and let the geometry place them. 935 of 1,227 went back to the same room, 89 went to another, and 203 got no room. For 174 of those 203, mostly plumbing and electrical terminals, the room reader found no solid body to test.

What the QC catches

The QC runs the checks an owner's review does:

  • required cells by stage (design, or handover with manufacturer, warranty and serial numbers);
  • duplicate keys;
  • references to floors, types, rooms or components that do not exist;
  • emails, ISO dates, numbers and pick lists.

It also flags a cell that holds its own column name. The Duplex model has SerialNumber typed into the serial number of all 99 components, and the same for the tag, barcode and dates. Someone filled in a template and never replaced it, and a check on blank cells alone would pass it.

It also found a problem every one of the 25 files shares: none names an email in its owner history. COBie keys every row to a contact by email, so every CreatedBy cell is blank. The page now asks for your email and uses it on rows that have no author.

Try it

Drop a model at marisstella.app/ids-model-check/cobie.html, or run node cli.mjs --cobie model.ifc -o handover.xlsx --from-geometry from the repository. --cobie-qc workbook.xlsx checks a workbook from Revit's COBie Extension or anything else. The method and every number are in eval/cobie-2026-11-23.md. It is free, MIT licensed, and not professional advice: your contract's COBie requirements decide what a deliverable needs.