A half-round wall has both ends on one plane, and that broke our curved-wall takeoff

Two 180-degree tunnel walls read 5.58 m2 too much outer face. The cause was not CSG cutters but geometry: both ends share one plane through the centre.

IFC Quantity Takeoff measures a curved wall's side area on its own facets: it sums the faces plane by plane, finds the centre of the bend, and sorts each plane into the outer face, the inner face, or neither (the ends, the reveals). It then checks the result against the wall's volume before trusting it. Two walls in a public tunnel model, ISSUE_129 in the web-ifc test set, kept failing that check. They are half rings, 1.8 m thick, round a 19.3 m axis.

An earlier run blamed the wall's construction. The engine writes a concave drawn outline as a fan of signed triangles, 362 pieces here and 157 of them negative, and the run took those negative pieces for cutters whose faces leaked into the result. That turned out to be wrong.

What it was. On a half ring, both end faces lie on the same plane, and that plane passes through the centre. Summed as one patch, the two ends have their centroid half-way between them, on the centre itself. Seen from the centre, a point on the centre faces every way at once, and the test happened to say "outer". The outer face read 98.36 + 5.58 = 103.94 m2, and 5.58 m2 is exactly the two ends (2 x 1.8 m x 1.55 m).

The two openings that cut through the ring, one near each end, did the same thing. Both are cut by the same two planes, one patch north of the centre and one south, so each pair's centroid sat where a plane of the face would be.

The fix. A real facet of a curved face lies round the foot of the perpendicular from the centre to its plane. Two patches either side of that foot do not, and neither does a plane through the centre. So each plane's area now has to stay within 45 degrees of that foot (an RMS distance from its second moment) before it counts toward a face. Both walls now match their own axis circle to 0.003%: 98.362 against 98.360 m2 outside, 89.597 against 89.595 inside, 1.7999 m wide against a type thickness of 1800 mm. With their openings taken out, the faces still close on the net volume to 0.01%.

Across the four public models with curved walls, no other wall's figure moved, gross or net. The bill gains the side area of two walls that store none: 327.41 m2 gross, 285.42 m2 net, up from a 22.83 m2 chord cut.

What it doesn't show: neither wall stores a side area, so the only check is against the file's own axis and volume. The 45-degree bound comes from the geometry, not from fitting it to data. Full numbers and the rerun commands: eval/half-round-ends-2026-11-23.md.

The tool is free, MIT licensed and runs in your browser; the model never leaves your machine. Its figures are estimates to check, not a priced bill.