One void threshold for every element moved slab areas on 4 of 11 models

Our free IFC takeoff now sets small-void thresholds per work section. One pair for everything added up to 7.2 m2 of slab area that a volume rule leaves alone.

Earlier today the free IFC Quantity Takeoff learned to leave small openings in, the way a method of measurement does. A pipe sleeve under some size isn't deducted from a wall's plaster or a slab's concrete. That first version took one pair of numbers for the whole model, an area threshold and a volume threshold.

Methods of measurement don't work that way. The threshold depends on the work section, and so does the figure it's judged by. Masonry voids are judged by area. In-situ concrete voids are judged by volume. Finishes have their own figure. With one pair, a concrete slab measured by volume also gets its area adjusted by the area threshold. A plaster covering measured by area also gets its volume adjusted.

What changed

The rule now takes a pair for each work section: walls, slabs and roofs, coverings and finishes, beams, columns and members, and everything else. A section you don't set uses the main pair. On the page, the "Openings" control has a By work section preset: walls and finishes by area (0.50 m²), slabs and frames by volume (0.05 m³). Under Custom thresholds, ticking "per work section" opens a small table to edit. On the command line:

node cli.mjs model.ifc --voids-up-to "0.5,0.05;slabs=0,0.05;coverings=0.5,0"

The bill-of-quantities CSV heading spells out the rule it was measured under. The preset is shaped like UK practice, but it isn't any standard's text. You still type the numbers your contract's method gives.

How much it moves on real models

We ran the single 0.50 m² / 0.05 m³ pair and the by-section preset over 11 public models. On 7 the bills were identical. On the other 4, the single pair adjusted figures that a per-section rule leaves alone:

ModelWhat the single pair also moved
HHS Office, architect (Revit)slab area +7.21 m², from 102 small slab openings
kleine_Wohnungslab area +2.93 m²
ARK_NUS schoolslab area −2.21 m² (a gross figure with its larger openings taken out)
schependomlaancovering volume +0.04 m³

Slab volumes and wall figures came out the same under both. The amounts are small, under 0.2% of any class's total, because these models have few small openings. But they land on lines an estimator prices by area, like a slab's soffit formwork or its finish. On a services-heavy building with hundreds of floor penetrations, the gap grows with the count.

Method, models and numbers are in eval/measure-sections-2026-11-20.md. Nobody has checked the result against a quantity surveyor's measured bill of one of these models yet. That's the outside check still missing.

The tool runs in your browser and nothing is uploaded. It isn't a measured survey or a cost estimate. Check every quantity against the drawings and your method of measurement.