Three exporters, three answers: a steel member's surface area in IFC

IDS Model Check now writes beams', columns' and members' missing surface areas from their bodies, following each exporter's convention: 1,479 of 1,544 match.

Paint, galvanising and fire protection on a steel frame are priced per square metre of steel. So an IDS file for a steel or precast model often asks every beam, column and member for two figures from Qto_BeamBaseQuantities and its sibling sets. OuterSurfaceArea is defined as the area of the side faces with the end caps left out. GrossSurfaceArea is the side faces plus both ends. When a model doesn't store them, IDS Model Check now measures them from the element's body and writes them into a copy of the model.

Why these two

The public test models from the web-ifc project are the corpus here. Before starting, the run counted which Qto_ figures those exports store that the fill could not yet measure. The surface areas came out on top: 2,740 stored OuterSurfaceArea and 460 GrossSurfaceArea figures on linear members, written by ARCHICAD, Tekla and Revit.

The measuring part is short

Take a straight member with square ends. Its side faces are the section's outline times the length. The takeoff engine underneath already cuts a body into convex pieces and knows its axis, and an earlier run wrote the outline code for slabs, so the beam case was mostly wiring. On the sample model an IPE 200 comes out at 0.768 m² per metre, the figure in the steel section tables. Bodies stored as polygons (faceted) are read from their faces: the faces square to the axis count as side area, but only when the faces left over are exactly two end caps. If they aren't, the axis is wrong for that body, and it gets no figure.

The exporters' part is not

Each measured figure was compared with what the exporter had stored:

  • ARCHICAD follows the definition. Outer is the side faces and Gross adds the ends: 114 of 114 Gross figures and 106 of 114 Outer figures matched.
  • Tekla stores the side faces plus the ends under both names, against the definition. Its tubes taught a second rule. Lifting eyes modelled as 60 mm hollow circles stored half of what was first measured, because the bore had been counted. Tekla counts only the outside face of a tube. With both rules, 1,373 of 1,428 Outer and 284 of 296 Gross figures match.
  • Revit (one school model) stores the side faces under both names. Every figure is also a million times too big: the export wrote mm² under a file unit of m². This is the same model that wrote its room volumes in litres. Revit therefore gets Outer only.

For any other tool the fill writes Gross, where ARCHICAD and Tekla agree with the definition. It writes Outer only when the ends are under 2% of the total, which makes the two conventions the same number. ARCHICAD and Revit tubes are left for a person to fill in, because no public export shows what those tools store for one.

End to end

The stored figures were hidden and the fill was asked for both names on every linear member in the seven models. It wrote 4,041 values. Each passes the fill's own re-read, and IfcTester, the independent IDS checker, moves exactly the written elements from fail to pass.

The misses are listed in the write-up. The biggest group is 40 small Tekla tube pieces whose stored 0.012 m² is rounded to three decimals. Next come 12 beams where Tekla adds a constant 0.2016 m² that no face of the body explains.

The tool is free and runs in the browser. Results are estimates measured from the model's geometry, not professional advice, so check them before you price work from them.

All writing · More in Tools and projects · More on IDS Model Check · All tools and research