Earlier today the free IDS checker learned to measure a wall's Qto_ Length and Height when the model leaves them out. That only covered walls with a straight Axis curve and an extruded body. Two kinds of wall were skipped: walls exported as a faceted brep, where the extrusion is gone and only faces are left, and walls with no Axis at all. One public sample, ISSUE_034 HouseZ, has 140 walls and none of them could be measured.
Reading a brep the same way
The length is measured on the plane halfway through the wall's thickness: a horizontal line along the wall, at the level where the wall is longest. For an extruded body, that line is tested against a few convex pieces. A brep is a closed shell, often not convex. The quantity-takeoff engine the checker shares already has a way to break any closed shell into signed tetrahedra. It fans each face to the shell's centre, and the signs add up to exactly "inside" or "outside". So the same line test reads a brep with no new geometry code.
Height is harder. An extruded wall that a roof clips still tells you its extrusion depth, which is what Revit stores. ARCHICAD stores the clipped wall's tallest point instead, so the first pass offered no Height for a clipped wall. A brep has the clip baked into its faces, so the two readings can't be told apart. The fill now offers a brep wall's Height only when the top is level along the whole wall. There both conventions give the same number. A gable wall, or a wall with a slab notch in its top, goes to the to-fill table for a person to type in.
With no axis, the direction comes from the body. A wall is thinnest across its side faces, so the length runs at right angles to that face normal.
Checking it on walls whose answer is known
None of the newly measured walls stores a Length, so the new paths were run on the 492 walls that do (three Revit and two ARCHICAD exports), with the axis ignored:
- Direction from the body: the same length as the axis reading on 492 of 492 walls.
- Every body handed over as closed shells and fanned into tetrahedra (the path a non-convex brep takes): the same length again on 492 of 492. The level-top rule offered 419 heights, and all 419 were within 2% of the stored figure. It held back 73, the walls a roof, slab or notch cuts.
One guard came out of the tests. An L-shaped body's middle line runs through one arm only, so a 5 m corner wall read as 0.3 m. A length shorter than the body is thick is now refused. That dropped four walls the first pass had measured. None of them stored a length to compare with.
What it changes
On the 15 public models, 3,247 of 3,312 walls are now measured, up from 2,955. HouseZ went from 0 to 134. On the seven models the new paths reach, filling Length and Height from an IDS left 100 walls failing instead of
- All 3,478 values written read back passing in the checker and in
IfcOpenShell's IfcTester, and no element IfcTester passed before fails after.
One open question: Revit writes its own wall length into a property set, measured along the wall's location line. On one French tunnel model the body is up to a few metres shorter than that figure, on extruded and brep walls of the same type alike. The fill writes the body's length, as it does for every wall. Full numbers, and what is left (a cut-top brep wall's Height, curved walls), are in eval/wall-brep-lengths-2026-11-21.md.
The checker and its fill run in the browser, and the model never leaves the machine. They are estimates from the model's geometry, not a surveyor's measurement.