The portfolio has a new free tool: a psychrometric calculator. You fix a point of moist air with any two of dry bulb, wet bulb, dew point, relative humidity, humidity ratio or enthalpy. It also takes the altitude. Then you can send the air through a process: mixing two airstreams, a cooling coil, sensible heating or an evaporative cooler. It plots the result on a psychrometric chart drawn for that pressure. It runs in the browser and nothing is uploaded.
Why build one
The repository already had an HVAC load calculator and a wall condensation check. Each has a few lines of moist-air arithmetic inside it, but nothing let you just ask "what is this air?" A text answer is also a poor fit for these questions. The wet bulb, and any pair of inputs without a dry bulb, needs an iterative solve. Finding a coil's apparatus dew point means intersecting a line with the saturation curve. And altitude changes every answer, while a reply from memory tends to read a sea-level chart.
A coil, worked through
The example on the page is a coil at the entering condition used for AHRI ratings, 80 °F dry bulb and 67 °F wet bulb. The air leaves at 55/54, with 1,200 cfm across the coil at sea level. The calculator gives:
- 46,178 Btu/h, or 3.85 tons, total;
- a sensible heat ratio of 0.69, with 1.58 gallons an hour of condensate;
- an apparatus dew point of 52.5 °F and a bypass factor of 0.09.
The field rule "4.5 × cfm × Δh" gives 47,927 Btu/h for the same coil, 3.8% high. The 4.5 assumes standard air at 13.33 cubic feet per pound, and air at 80 °F and 51% humidity takes up 13.85. The guide walks through each step.
Then move it to Denver
Keep the same thermometer readings and the same airflow, and set the altitude to 5,280 ft. The total pressure drops to 12.10 psia, so the same wet bulb now means more water in each pound of air. Entering air holds 99.9 grains per pound instead of 78.2. The total load falls a little, to 43,428 Btu/h, because each cubic foot holds less air. The bigger change is the split: the sensible heat ratio drops from 0.69 to 0.61.
A technician who reads a sea-level chart at altitude gets the moisture wrong by more than a fifth. They also get the coil's balance between cooling and drying wrong. That is the reason the tool asks for altitude before anything else.
How it was checked
The engine follows Chapter 1 of ASHRAE Fundamentals. Saturation pressure uses the Hyland-Wexler formulas, over ice below freezing. The unit tests check:
- the saturation pressure against IAPWS steam-table values for water and ice, to 0.05%;
- the standard-atmosphere pressures against ASHRAE's table;
- a hand-worked wet-bulb calculation;
- that every one of the 13 workable pairs of inputs recovers the same point, at four states, in both unit systems;
- that mixing conserves mass and energy;
- that the ADP lies on the coil line at saturation;
- that every number in the guide matches the engine.
It has not been compared with a commercial psychrometric program, and the page says so.
Next
The obvious next step is to plot a whole system on one chart: outdoor air mixed with return air, the mix through the coil, then reheat. After that, a link from the load calculator's design conditions straight into the chart.