What a filter costs the ducts: a free duct sizer that starts from the blower's static pressure

The HVAC load calculator now sizes every duct by friction rate. On its example house, a filter losing 0.1 in. w.c. more turns an 8-inch run into a 10-inch one.

The room-by-room HVAC load calculator has always ended with a number per room: the airflow a duct designer would size that room's run for. It stopped there. Its sibling, the wall-framing takeoff, counts duct sticks and flex rolls but says plainly that it does no duct sizing. So the step between "this bedroom needs 154 cfm" and "run an 8-inch duct to it" was left to a rule of thumb or a cardboard duct slide rule.

It now has a duct sizing page and a --ducts flag on the CLI.

How it sizes

The method is the friction-rate one most residential duct design uses, built here from open physics rather than anyone's tables:

  1. What the ducts may spend. The blower is rated to push its airflow against some external static pressure, often 0.5 in. w.c. The coil, the filter, a supply register and a return grille each take a share at that airflow. What is left is all the ductwork gets.
  2. Over how far. Spread that over the longest supply path plus the longest return path, counted as total effective length (straight feet plus the equivalent length of every fitting, which you type from your fitting maker's data). The result is the design friction rate, in inches of water per 100 ft.
  3. Each run. For every listed round size, the loss per 100 ft comes from Darcy-Weisbach with the Colebrook friction factor, at the air density for the house's elevation. A run gets the smallest size at or under the friction rate and under a velocity limit. Trunks carry the sum of the rooms you assign to them, with a rectangular equivalent by Huebscher's formula. Each run also reports what its balancing damper must throttle, because a short run near the air handler has pressure the long run used.

As a check on the units, the tests compare the engine with a widely quoted power-law fit for galvanized duct, Δp = 0.109136 q^1.9 / D^5.02. At the default roughness of 0.0003 ft the engine comes out 3 to 9% lower across 50 to 2,000 cfm; at 0.0005 ft it lands within 5% of the fit at every point tested.

What the example house shows

The example is the calculator's illustrative 1,800 ft² ranch (made-up inputs, not a measured house), with effective lengths of 90 to 185 ft per run and a 60 ft return. All figures below are the engine's output.

  • With a 0.5 in. w.c. blower and the page's example component losses (coil 0.20, filter 0.10, register and grille 0.03 each), the ducts get 0.14 in. w.c., a design friction rate of 0.057 per 100 ft. The bedrooms come out at 7 and 8 in., the living room at 10 in., the two trunks at 12 and 14 in., the central return at 18 in.
  • Swap in a filter that loses 0.2 instead of 0.1 (a denser filter at the same airflow) and the ducts are left with 0.04 in. w.c.: the friction rate falls to 0.016, the primary bedroom run grows from 8 to 10 in., the living room from 10 to 14 in., the return from 18 to 22 in., and the page warns that the ducts are coming out large. Push the filter loss to 0.25 and the components alone use more than the blower has; the page refuses to size anything and says why.
  • A blower rated for 0.8 in. w.c. instead of 0.5 lifts the friction rate to 0.180, and every bedroom run shrinks by one or two sizes.
  • Flex pulled tight (0.003 ft roughness, a rough assumption the page labels as such) makes the living room run 12 in. instead of 10 and the primary bedroom 9 instead of 8. Flex that sags loses much more.

The filter line is the one worth taking away. The pressure a filter costs comes straight out of the ductwork's budget, and on a system with 0.14 in. to spare, a tenth of an inch is most of it.

What it does not do

It is not ACCA Manual D and uses none of its tables or fitting equivalent lengths. It sizes each trunk for the air at its start rather than reducing it section by section, and it does not check register throw or noise, duct heat gain or leakage, or whether the blower's fan curve actually delivers the airflow at the resulting pressure. The results are estimates, not engineering advice; many permits need a duct design from approved software or a qualified designer.

The page runs in the browser and uploads nothing. The engine is ventures/hvac-load-calc/duct.mjs, MIT licensed.