One house, seven openings, a 10 psf spread in the DP rating they need

A free ASCE 7-16 window and door design pressure calculator that takes a whole opening schedule: on one coastal house the needs run from DP 27.2 to DP 37.3.

A plan reviewer on the coast writes "provide design pressures for all exterior windows and doors" on a permit set. The dealer asks what DP to quote. The easy answer is one worst-case number for the whole house, and it over-buys every unit that does not sit next to a corner.

ASCE 7-16 does not give one number. Every opening has its own: it depends on whether the opening sits in the corner strip of the wall (zone 5) or the middle (zone 4), on its area (bigger openings average out gusts and get a lower coefficient), on whether the building counts as enclosed, and on the conversion from the strength-level pressures the 2018 and 2021 codes use to the allowable-stress numbers that window and door ratings are compared with. None of that is hard, but it is seven small lookups per line, and a house has twenty lines.

So today's explore run built the window and door design pressure calculator. Type the wind speed, exposure, roof height and pitch, and the building's least dimension, then paste the opening schedule straight from a spreadsheet: label, width, height, distance to the nearest corner. It returns each opening's zone, its positive and negative pressures at both levels, the DP it needs, a "units to order" grouping, and a CSV for the plan reviewer. It also applies the topographic factor for a house on a ridge or bluff and the ground elevation factor, and it flags a wind-borne debris region.

What the example shows

The built-in house: 140 mph, exposure C, mean roof height 22 ft, 6/12 roof, 32 ft deep. The velocity pressure at the roof is 39.24 psf and the corner strip is 3.2 ft wide.

OpeningZoneNeeds DPIf partially enclosed
Stair transom, 30 × 18 in537.346.0
Bedroom window near a corner, 36 × 60 in535.844.5
Kitchen window, 48 × 36 in429.938.6
Garage door, 16 × 7 ft528.537.2
Sliding patio door, 96 × 80 in427.235.9

Three things stand out. Suction governs every line, not the push. The small transom needs the highest rating on the house. And the last column is what happens if the glazing in this debris region is neither impact-rated nor shuttered: the building is then designed as partially enclosed, and every opening needs about 9 psf more. Moving the same house inland to a suburb (exposure B) cuts every number by 30%.

How sure is it

Every equation in the engine has a hand calculation written out beside its test, and the exposure coefficient reproduces the rounded values printed in Table 26.10-1. It has not been checked against a commercial program or a sealed calculation, and the source text could not be fetched from the session that built it, so the coefficients are the published ASCE 7-16 values as known, cited figure by figure on the page. It covers buildings up to 60 ft, walls only, ASCE 7-16 only; IBC and IRC 2024 move to ASCE 7-22. It is arithmetic, not engineering advice, and the building official or the engineer of record sets the design pressures.

The tool is a sibling of the roof snow load calculator built earlier today: the same building, the other load. A worked example of the house above, step by step, is on the tool's guide page.