Will the wind lift the roof or rack the walls of a shed?

The shed designer now checks rafter ties for uplift and walls for racking. The ties have room to spare; a 4 ft door centred in an 8 ft gable end does not.

Tools and projects · 2 min read · Source
shed-designerwindstructure

The shed designer already checked rafters, headers and studs under wind and snow. It took two wind paths on trust: the metal tie that holds each rafter down to the wall, and the siding panels that keep the walls from racking into a parallelogram. Both are now checked, against published values.

Uplift at the rafter ties. Each rafter end gets one tie:

  • a Simpson H2.5A hurricane tie on a notched (birdsmouth) seat;
  • a Simpson VPA2 variable-pitch connector on a connector seat.

Simpson's 2024 catalog gives their allowable uplift in spruce-pine-fir framing as 615 lb and 220 lb. The uplift on a tie is ASCE 7's allowable-stress combination 0.6D + 0.6W:

  • the wind pressure you set, acting up on the rafter's strip of roof and again under the overhang;
  • less 0.6 of the roof's own weight.

At 20 psf:

DesignTieNet uplift a tieHolds to
Starter 8x12VPA225 lb72 psf
8x12 classicH2.5A43 lb99 psf
10x12H2.5A47 lb87 psf
12x16H2.5A56 lb78 psf

The ties have room to spare. The "holds to" column is there because the tool takes one wind pressure for the whole shed. ASCE 7 gives higher pressures near roof edges and corners, so compare your local figure with it, not with 20.

Racking. Wind on the long side of a shed has to reach the ground through the two short walls, and the siding nailed to their studs is what stops them folding over. The check uses the shear-wall values in AWC's SDPWS (2015, Table 4.3A):

  • T1-11 is plywood siding: 450 plf at 6" nailing. Halved for allowable stress and reduced for spruce-pine-fir studs, that is 207 plf.
  • Lap siding over 7/16" OSB counts as OSB sheathing: 308 plf.
  • Only full-height panels count. A panel narrower than the wall's height divided by 3.5 counts for nothing, and one between h/2 and h/3.5 counts for less.

The presets come out at 23% to 58%. The weak spot is a door in a short wall. Put a 4 ft door in the middle of an 8 ft gable end and it leaves two 24" panels on a 96" wall, a 4:1 ratio, so that wall braces nothing. The other gable wall can take the whole load only if the roof can carry the twist to the long walls. SDPWS allows that for a one-storey open front no deeper than it is wide (1:1). An 8x8 qualifies. An 8x10 or 8x12 with that door does not, and the check fails it.

Of 24 door variations we tried on the gable ends of the presets, 7 failed this way. The fixes:

  • a narrower door;
  • a full-height braced panel beside it;
  • the door on a long wall;
  • an engineered portal frame or hold-downs (the tool does not model these).

What is still not checked. The hold-downs at the ends of each braced panel, and anything tying the shed to the ground. A shed on blocks is held down by its weight alone, which is a separate question and the next check worth writing.

All of this is screening with stated assumptions, not an engineer's review, and the plans are not engineered or code-checked.