What DP rating do my windows need?

A plan reviewer asks for "design pressures for all exterior windows and doors", a dealer asks what DP to quote, and the answer is not one number for the house. This page works one house through ASCE 7-16, the edition the 2018 and 2021 IBC and IRC adopt, the way the calculator does it.

The house

Two storeys near the coast, basic wind speed V = 140 mph, exposure C (open terrain), mean roof height 22 ft, a 6/12 roof, 32 ft deep, enclosed, flat site. Seven lines of openings, from a 30 × 18 in stair transom to a 16 ft garage door.

1. Velocity pressure at the roof height

For exposure C, Table 26.10-1 gives Kh = 2.01 (22/900)^(2/9.5) = 0.920. With Kzt = 1 (flat site), Kd = 0.85 for components and cladding and Ke = 1:

qh = 0.00256 × 0.920 × 1 × 0.85 × 1 × 140² = 39.24 psf.

The same house in a suburb (exposure B) has Kh = 0.641 and qh = 27.35 psf: exposure alone changes every pressure on this page by 30%.

2. Which openings are near a corner

Figure 30.3-1 calls a strip of width a at each wall corner zone 5. a is the smaller of 10% of the least horizontal dimension (3.2 ft) and 40% of h (8.8 ft), but at least 3 ft: a = 3.2 ft. The bedroom window 1.5 ft from the corner and the garage door 2 ft from it are zone 5; the rest are zone 4.

3. Pressure coefficients by size

The wall coefficient falls with the logarithm of the opening's area between 10 and 500 ft². The 3 × 5 ft bedroom window (15 ft², zone 5) gets (GCp) = +0.969 and −1.338; the 3.75 ft² transom keeps the full +1.0 and −1.4; the 112 ft² garage door drops to +0.815 and −1.029. The roof is steeper than 10°, so there is no 10% reduction.

4. Net pressure and the DP

An enclosed building takes (GCpi) = ±0.18, in whichever direction adds. For the bedroom window:

p− = 39.24 × (−1.338 − 0.18) = −59.6 psf strength level, and 0.6 × that = 35.74 psf allowable-stress. Window ratings are compared with the allowable-stress number, so the window needs DP 35.8 (rounded up). Suction governs: the positive side needs only 27.1.

OpeningArea ft²ZoneNeeds DPIf partially enclosed
Front bedroom window15.0535.844.5
Living room picture window30.0428.236.9
Kitchen window12.0429.938.6
Sliding patio door53.3427.235.9
Entry door with sidelites36.4427.936.6
Garage door112.0528.537.2
Stair transom3.8537.346.0

5. The debris region changes the enclosure

At 140 mph the site is in a wind-borne debris region (Section 26.12.3.1). If the glazing is impact-rated or shuttered the building stays enclosed and the middle column applies. If not, it is designed as partially enclosed, (GCpi) = ±0.55, and every opening needs about 9 psf more, the last column. Either way the debris region adds a cost: impact glass or shutters, or higher-rated units everywhere.

Common questions

Do all the windows on a house need the same DP rating?

No. Openings near a corner (zone 5) and small openings take higher suction. In the worked example the highest need is DP 37.3 for a small transom near a corner and the lowest DP 27.2 for a sliding door mid-wall, on the same house.

How much does a partially enclosed building raise the DP?

A lot. Moving the internal pressure coefficient from ±0.18 to ±0.55 adds 0.37 qh to every opening's net pressure. In the worked example the bedroom window goes from DP 35.8 to DP 44.5.