How many solar panels per string?

The quick answer people reach for is the inverter's maximum DC voltage divided by the module's Voc. With a 600 V limit and a 49.5 V module that gives 12. On a -20 C morning those 12 modules make about 666 V, and the right answer is 10.

Size your strings with the free calculator

Who this is for

Anyone laying out string inverters: installers checking a design before the permit set, designers comparing inverters, and people building their own system who want to know why the inverter maker's tool rejected a string. If your system uses microinverters or DC optimisers, the module-level electronics set the string rules instead, and this check is not the one you need.

Two limits, two temperatures

Module voltage goes up as cells get colder and down as they get hotter. A string has to satisfy both ends:

Worked example

An invented module, inverter and site (example numbers, not a real product): Voc 49.5 V, Vmp 41.4 V, Isc 10.3 A, Voc coefficient -0.27 %/C, Vmp coefficient -0.35 %/C, NOCT 45 C; inverter 600 V maximum, MPPT 100 to 550 V, two MPPT inputs that each accept 26 A short-circuit; site extreme minimum -20 C, hot-day air 35 C.

StepArithmeticResult
Voc per module at -20 C49.5 x (1 + -0.0027 x (-20 - 25))55.51 V
Longest string600 / 55.51, rounded down10 modules
Hot-day cell temperature35 + (45 - 20) x 1000/80066.25 C
Vmp per module at 66.25 C41.4 x (1 + -0.0035 x 41.25)35.42 V
Shortest string100 / 35.42, rounded up3 modules
Vmp per module at -20 C41.4 x (1 + 0.0035 x 45)47.92 V
Longest string that stays under the 550 V MPPT maximum when cold550 / 47.92, rounded down11 (not binding)
Design current per string1.25 x 10.3 (NEC 690.8(A)(1))12.88 A
Strings per MPPT input26 / 12.88, rounded down2
Minimum conductor ampacity per string1.25 x 12.88 (690.8(B)), before corrections16.09 A

With 24 modules on the job, two layouts use every module: three strings of 8 (two on one input, one on the other) or four strings of 6 (two per input). Two strings of 12 would be over the cold-voltage limit. The calculator lists every option with its DC/AC ratio and flags lengths that leave the MPPT window when cold.

Where the inputs come from

When to use something else

The inverter maker's own string-sizing tool knows its equipment's limits better than a datasheet does; use it for the final design. Microinverter and optimiser systems follow the module-level device's rules. And the code edition your jurisdiction adopted, not this page, decides the voltage limit and the conductor rules.

Common questions

Why can't I just divide the inverter's maximum voltage by the module's Voc?

The datasheet Voc is measured at 25 C. Module voltage rises as cells get colder, so on the coldest morning each module makes more than its rating. In the example on this page, 600 V divided by 49.5 V says 12 modules, but at -20 C each module makes 55.51 V and only 10 fit.

What sets the minimum number of modules in a string?

The inverter's MPPT minimum voltage against the module's maximum-power voltage on the hottest afternoon, when cells run well above the air temperature. Divide the MPPT minimum by the hot-day Vmp per module and round up.

Does this apply to microinverters or DC optimisers?

No. With module-level power electronics the device's own rules set the string length, so use the maker's sizing guidance instead.