1. The blower and what is in the way
The blower's rated external static pressure at your design airflow is on the air handler's fan table. The losses below are example values: use your coil's, filter's and register maker's figures at your airflow.
2. Supply runs
Total effective length is the run's straight feet from the air handler to the register, trunk included, plus the equivalent length of every elbow, boot and takeoff on the way. The page has no fitting table: use your fitting maker's equivalent lengths. Rooms with the same trunk name share a trunk.
Bring rooms from the load calculator
Paste the house JSON the load calculator exports. Each room's design airflow fills a run; lengths stay as typed (or come from the file's ducts block). The second button puts this design in the box as a ducts block, which node cli.mjs house.json --ducts reads.
Result
Runs
| Run | cfm | TEL ft | Round | ft/min | in/100 ft | Set by | Damper in. w.c. |
|---|
"Set by" says whether the friction rate or the velocity limit chose the size (the next size down breaks it). The damper column is the static pressure a run's balancing damper must take up because its path is shorter than the longest: short runs near the air handler need the most throttling.
Trunks
| Trunk | cfm | Round | Rectangular | ft/min | in/100 ft |
|---|
A trunk carries the sum of the rooms you gave it, at the start, before any takeoff. The rectangular size is the narrowest width, at the height you set, whose circular equivalent (Huebscher) is at least the round size.